Master’s thesis focusing on the passive cooling supply of a virtual single office room, with passive house related construction standard, located in Munich. Nocturnal radiative cooling is used by a flat plate collector to provide cooling power at night, that refrigerates water in a thermal energy storage (TES). Chilled water in the TES provides a heat sink by day. Then, it is used to cool down the investigated single office room with the ceiling cooling and the mechanical ventilation when there is a cooling demand at daytime. A sufficient cooling for the office room is crucial, where among other things the dependency of the collector area, the TES volume and the room area is investigated. The plant concept is simulated with the thermal building simulation tool TRNSYS 17 using Genopt to optimize the parameters of the system.
«
Master’s thesis focusing on the passive cooling supply of a virtual single office room, with passive house related construction standard, located in Munich. Nocturnal radiative cooling is used by a flat plate collector to provide cooling power at night, that refrigerates water in a thermal energy storage (TES). Chilled water in the TES provides a heat sink by day. Then, it is used to cool down the investigated single office room with the ceiling cooling and the mechanical ventilation when there...
»